UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
8 Technical Specifications
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
EN61000-4-3
IEC61000-4-8
IEC61000-4-11
8.5 Mains Input Electrical Specifications
380 V AC, 400 V AC, or 415 V AC (line voltage)
80–280 V AC (phase voltage)
At 40°C: The UPS works at full load when the voltage is
187–280 V AC and is derated to 40% load when the voltage
is 187–80 V AC.
At 30°C: The UPS works at full load when the voltage is
176–280 V AC and is derated to 40% load when the voltage
is 176–80 V AC.
> 0.99 (full load); > 0.98 (half load)
< 3% (full linear load); < 5% (full non-linear load)
8.6 Bypass Input Electrical Specifications
380 V AC, 400 V AC, or 415 V AC (line voltage)
Three-phase, four-wire, and PE
The mains input and bypass input share a power source or use different
power sources.