UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power
Modules)
Issue
02
Date
2017-02-25
HUAWEI TECHNOLOGIES CO., LTD.

Table of Contents

Other manuals for Huawei UPS5000-E-300K-SMT

Questions and Answers

  • M
    Melissa WrightAug 9, 2025
    What to do if the Huawei Control Unit inverter is not normal?
    • D
      Diana PriceAug 9, 2025
      If your Huawei Control Unit inverter isn't working normally, it might be due to an overload or a short circuit. Try reducing the load or fixing any short circuits. Alternatively, the power module could be faulty, in which case you should replace it.
  • M
    Melinda EvansAug 15, 2025
    Why does my Huawei Control Unit UPS work in bypass mode and not transfer to inverter mode?
    • J
      jeanetteallenAug 15, 2025
      If the Huawei Control Unit UPS is stuck in bypass mode and won't switch to inverter mode, the working mode might be incorrectly set; ensure it's set correctly. Also, if the bypass transfer times have reached their limit, clear the faults on the LCD.
  • S
    Stephanie StricklandAug 21, 2025
    What to do if the Huawei Control Unit charger generates an alarm?
    • M
      Morgan FryAug 21, 2025
      If the Huawei Control Unit charger generates an alarm, it could be due to several reasons. The charger itself might be failing, or it could be experiencing overcurrent or undervoltage. In the case of charger failure or overcurrent, replace the power module. If it's undervoltage, check if the configured number of batteries is correct. If it is correct and the alarm persists, replace the power module.
  • D
    denniswestAug 27, 2025
    What to do if the Huawei Control Unit bypass is not normal?
    • D
      Dana ScottAug 27, 2025
      If the Huawei Control Unit bypass is not working normally, it could be due to a damaged bypass thyristor, which requires replacing the bypass module. Another reason could be the bypass module experiencing overtemperature. In this case, reduce the load or improve ventilation.
  • H
    hamptonchristopherSep 2, 2025
    Why is the Huawei Control Unit rectifier not working, and the bus voltage is not boosted?
    • R
      Ronnie WeberSep 2, 2025
      If the rectifier of your Huawei Control Unit isn't working and the bus voltage isn't being boosted, it might be because the mains voltage is too high (above 280 V) or too low (below 80 V). Check the mains voltage against these thresholds, and if it's outside this range, contact the electric power company.

Summary

User Manual

UPS5000-E-(50 kVA-300 kVA) User Manual

Specifies the model of the UPS system and the manual title.

1 Safety Precautions

1.1 General Safety

Covers fundamental safety precautions for personnel and equipment.

1.2 Electrical Safety

Addresses safety measures related to high voltage and leakage current.

1.4 Battery Safety

Provides essential safety precautions for handling and maintaining batteries.

2 Overview

2.2 Working Principle

Describes how the UPS operates and its internal working principles.

3 Installation

3.1 Installation Preparations

Covers essential steps before starting the UPS installation.

3.2 Installing a Single UPS

Step-by-step guide for installing a single UPS unit.

3.2.5 Routing Cables (UPS5000-E-200 K-SM)

Instructions for routing cables from the top of the UPS cabinet.

3.3 Installing a Parallel System

Steps for installing UPS units in a parallel configuration.

3.3.2 Connecting Power Cables

Instructions for connecting power cables in a parallel UPS system.

3.4 Installation Verification

Checklist for verifying the correct installation of the UPS system.

4 User Interface

4.1 LCD Interface

Explains the operation and features of the UPS's LCD interface.

5 Operations

5.1 Powering On and Starting the UPS

Step-by-step guide to safely power on and start the UPS system.

5.2 Shutting Down and Powering Off the UPS

Procedure for safely shutting down and powering off the UPS system.

5.6 Testing Batteries

Procedures for conducting battery tests like forced charging and capacity tests.

6 Routine Maintenance

6.2 Battery Maintenance

Guidelines and procedures for maintaining the UPS battery system.

7 Troubleshooting

8 Technical Specifications

8.7 Battery Specifications

Details the electrical specifications and configurations for the UPS batteries.

A (Optional) TN-C System Application

C Alarm List

Huawei UPS5000-E-300K-SMT Specifications

General IconGeneral
ModelUPS5000-E-300K-SMT
Rated Capacity300 kVA
Frequency50/60 Hz
Relative Humidity0% to 95% (non-condensing)
Input Voltage380/400/415 VAC
Output Voltage380/400/415 VAC
Efficiency (AC-AC)≥ 95%
Communication PortsRS485, SNMP, USB, Dry Contact
Operating Temperature0°C to 40°C
Battery TypeValve-regulated lead-acid (VRLA) / Lithium-ion battery
Noise Level<65 dB(A)