UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
240
Figure 5-50 Confirmation message
Step 4 Tap Yes. A message is displayed, indicating that the hibernation function is set successfully.
Step 5 Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The default value is
30.
----End
5.12.2 WebUI
Procedure
Step 1 On the login page, enter a user name and password, and click Login.
Step 2 Choose Monitoring > Param. Settings > Advanced Param., as shown in Figure 5-51.
Figure 5-51 Hibernation parameters on the WebUI