Figure 5-25 Starting a forced equalized charging test
Tap Stop next to Forced Equalized Charging in any of the following cases:
The forced equalized charging test duration reaches the forced equalized charging protection time
(12–24 h, 18 h by default).
The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.
An alarm is generated.
----End
5.6.2 Shallow Discharge Test
Context
Before a shallow discharge test, ensure that:
The UPS works in normal mode with a load ratio fluctuation less than 10%.
The UPS has generated no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated.
Procedure
Step 1 On the main screen of the LCD, tap System Info. Tap . The Maintenance screen is
displayed.
Step 2 (Optional) If no user is logged in, enter a user name and a password, and then tap .
For details about default user names, preset passwords, and user rights, see Table 4-5.