UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
8 Technical Specifications
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
252
Item
UPS5000-E-200K-SM/FM
UPS5000-E-300K-SM/S
MT
EN61000-4-3
IEC61000-4-8
IEC61000-4-11
8.5 Mains Input Electrical Specifications
Item
UPS5000-E-200K-SM/
FM
UPS5000-E-300K-SM/SMT
Input system
Three-phase, five-wire
Rated input voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input voltage
80280 V AC (phase voltage)
At 40°C: The UPS works at full load when the voltage is
187280 V AC and is derated to 40% load when the voltage
is 18780 V AC.
At 30°C: The UPS works at full load when the voltage is
176280 V AC and is derated to 40% load when the voltage
is 17680 V AC.
Rated frequency
50 Hz/60 Hz
Input frequency
4070 Hz
Input PF
> 0.99 (full load); > 0.98 (half load)
THDi
< 3% (full linear load); < 5% (full non-linear load)
8.6 Bypass Input Electrical Specifications
Item
UPS5000-E-200K-SM/FM
UPS5000-E-300K-SM/SM
T
Rated input
voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input system
Three-phase, four-wire, and PE
Rated
frequency
50 Hz/60 Hz
Input mode
The mains input and bypass input share a power source or use different
power sources.