UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
234
Figure 5-41 EPO alarm displayed on the WebUI
After you press the EPO button, the EPO and No power supplied alarms are displayed on the LCD.
5.10 Clearing the EPO State
Procedure
Step 1 Clear the EPO state. Ensure that the EPO button connected to the dry contact card is not in the
EPO state.
Step 2 Clear the EPO alarm.
On the LCD
On the LCD, choose System Info > Alarms and tap Clear Faults. If you have not
logged in, a login screen is displayed. Enter a user name and password, and tap
.