UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
241
Step 3 On the WebUI, set Paral. sys. hibernate to Enable, and click Submit.
Click Submit after you set the parameter on the WebUI.
Step 4 Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The default value is
30.
----End