UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3.2.5 Routing Cables (UPS5000-E-200K-SM)
3.2.5.1 Routing Cables from the Top
Context
Route cables for the UPS from inside out and from bottom up.
After routing cables, use firestop putty to fill in the gap between the cables and the cabinet.
Procedure
Step 1 Ensure the maintenance bypass switch is OFF. Open the front door, and remove the cover
from the power distribution subrack, as shown in Figure 3-29. The positioning of the copper
bars is shown in Figure 3-30
Figure 3-29 Removing the cover