Connect the possible faulty optimizer to the PV string.
Set DC SWITCH to ON. If the inverter status is Shutdown: Command, choose
Maintenance > Inverter ON/OFF, and send a startup command. View alarm
information.
If no Low insulation resistance alarm is reported 1 minute after the DC
side is powered on, the fault is on the possible faulty PV module.
If the Low insulation resistance alarm is reported 1 minute after the DC
side is powered on, the fault is on the possible faulty optimizer.
Log in to the app, choose Maintenance > Inverter ON/OFF on the home
screen, and send a shutdown command. Set DC SWITCH to OFF, replace the
faulty component, and complete troubleshooting the insulation resistance
fault. Go to Step 2 and check rest of the PV strings one by one. Then, go to
Step 8.
Step 8 Set DC SWITCH to ON. If the inverter status is Shutdown: Command, choose
Maintenance > Inverter ON/OFF, and send a startup command.
----End
SUN2000-(12KTL-25KTL)-M5 Series
User Manual D Locating Insulation Resistance Faults
Issue 10 (2024-05-14) Copyright © Huawei Digital Power Technologies Co., Ltd. 99

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-12KTL-M5 Series and is the answer not in the manual?

Huawei SUN2000-12KTL-M5 Series Specifications

General IconGeneral
BrandHuawei
ModelSUN2000-12KTL-M5 Series
CategoryInverter
LanguageEnglish

Related product manuals