5
If outdoor copper-core cables are used, select copper wiring terminals. For details about the
requirements for cables and terminals of other materials, see the user manual.
4
Installing Cables
Installation Preparations
4.1
No.
Item
Type
Specifications
Description
1
PE cable
Single
-core
outdoor copper
cable
Conductor cross
-
sectional area ≥ S/2
[1]
(S
is the conductor cross
-
sectional area of the AC
output power cable.)
If you choose the
ground point on the
chassis shell for
connecting a PE
cable, prepare the PE
cable.
If you choose the
ground point in the
maintenance
compartment for
connecting a PE
cable, use a four-
core
AC output power
cable and do not
have to prepare a PE
cable.