Loading...
TP48200A-DT19C1, TP48200A-DT19C2,
TP48200A-HT19C1 and TP48200A-HT19C2 Telecom
Power
User Manual
A Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
98
Item
Specifications
Input voltage
-48 V DC
Service life
10 years
Operating temperature
-10°C to +45°C with 1120 W/m
2
solar radiation
Storage temperature
-40°C to +70°C
Altitude
< 4000 m
Relative humidity
5%-95% RH
Noise
< 65 dB (A)
A.7 TEC04C Specifications
Table A-7 TEC04C specifications
Item
Specifications
Rated voltage
-48 V DC
Rated cooling capacity (L32/L32)
200 W
Heating capacity
> 300 W
Rated Cooling Power Consumption
300 W
Operating environment
-40°C to +40°C
Relative humidity
5%-95% RH
Storage environment
-40°C to +70°C, complying with the ETS 300
019-1-1, Class 1.2.
Altitude
< 4700 m
Service life
10 years
Mean time between failures (MTBF)
> 100,000 hours
Dimensions (H x W x D)
400 mm x 180 mm x 200 mm
Weight
6.4 kg
Reverse connection prevention for DC power
Supported
Operating voltage
-36 V DC to -60 V DC
Temperature sensor
Detecting range: -20°C to +80°C (precision: ±C)