A Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
94
A Technical Specifications
A.1 Environmental Specifications
Table A-1 Environmental specifications
Item
Specifications
Operating temperature
-10°C to +45°C
Transportation temperature
-40°C to +70°C
Storage temperature
-40°C to +70°C
Operating humidity
5%-95% RH
Storage humidity
5%-95% RH
Altitude
0-4000 m
When the altitude ranges from 2000 m to 4000 m, the operating
temperature decreases by 1°C for each additional 200 m.
Noise level
Complies with GR487. Acoustic pressure level: <65dBA@1.5 m
A.2 Electrical Specifications
Table A-2 Electrical specifications
Item
Specifications
AC input
AC input system
TP48200A-DT19C1 and
TP48200A-HT19C1: 220/380 V AC
three-phase, four-wire and compatible
with 220 V AC single-phase
TP48200A-DT19C2 and
TP48200A-HT19C2: 110 V AC
dual-live wire
AC input voltage
85 V AC-300 V AC