7.2.3 Quarterly Maintenance 
Table 7-5 Quarterly maintenance tasks 
No battery alarm is 
generated. 
Identify the cause based on the alarm 
information. 
1.  The battery shell is 
intact, without acid 
leaks, deformation, 
or bulges. 
2.  The battery is free 
from dust or dirt. 
1.  Take photos of any deformed or faulty 
parts of batteries. 
2.  Check and record the charge voltage and 
current of the battery string as well as the 
voltage of each battery. 
3.  Check the battery surface temperature. 
4.  Keep deformed and bulged faulty batteries 
still for 30 minutes and then check and 
record open-circuit voltage of the faulty 
battery. 
5.  If the fault persists, contact Huawei 
technical support. 
Battery 
operating 
temperature 
1.  The service 
temperature of a 
working battery 
does not exceed 
45ºC. 
2.  The battery ambient 
temperature is 
25±5°C. 
1.  Identify the cause of the abnormal battery 
operating temperature. 
2.  If the fault persists, contact Huawei 
technical support. 
Parameters settings of 
battery capacity, battery 
number, battery charge 
current limit setting 
values meet 
requirements and match 
the actual value. 
 
7.2.4 Yearly Maintenance 
Table 7-6 Yearly maintenance tasks 
No battery alarm is 
generated. 
Identify the cause based on 
the alarm information. 
1.  The battery shell is 
intact, without acid 
leaks, deformation, or 
bulges. 
2.  The battery is free from 
1.  Take photos of any 
deformed or faulty parts 
of batteries. 
2.  Check and record the 
charge voltage and