UPS2000-A-(6 kVA-10 kVA) 
User Manual 
9 Technical Specifications 
 
Copyright © Huawei Technologies Co., Ltd. 
 
6 kVA/10 
kVA 
Standard 
Version with 
Standard 
Backup Time 
6 kVA/10 
kVA 
Standard 
Version 
with Long 
Backup 
Time 
6 kVA/10 
kVA 
Professional 
Version 
with 
Standard 
Backup 
Time 
6 kVA/10 
kVA 
Professional 
Version 
with Long 
Backup 
Time 
minute. The input circuit breaker may trip in advance. 
 
Load ≥ 150%: The UPS stops power output after 200 ms. The 
input circuit breaker may trip in advance (load is calculated 
based on the bypass currents). 
 
9.5 Output Electrical Specifications 
6 kVA/10 
kVA 
Standard 
Version with 
Standard 
Backup Time 
6 kVA/10 
kVA 
Standard 
Version 
with Long 
Backup 
Time 
6 kVA/10 
kVA 
Professional 
Version 
with 
Standard 
Backup 
Time 
6 kVA/10 
kVA 
Professional 
Version 
with Long 
Backup 
Time 
0.9 (When the power factor ranges from 0.5 to 1, the UPS2000-A 
with inductive load is not derated. When the power factor ranges 
from 0.5 to 1, the UPS2000-A with 80%–100% capacitive load is 
linearly derated.) 
220V AC/230V AC/240V AC 
(selected by setting a voltage 
level on the LCD.) 
208 V AC/220 V AC/230 V 
AC /240 V AC (selected by 
setting a voltage level on the 
LCD. The power is derated to 
0.9 in 208 V mode.) 
Total harmonic 
distortion of the 
output voltage 
waveform (THDv) 
 
≤ 5% (configured with a residual current device (RCD) with a 
0.7 power factor, and specified in the IEC62040 standards of 
THDv.) 
 
≤ 2% (resistive load. Each harmonic meets the limit specified 
by the IEC62040.)