8 Troubleshooting 
 
 
If the UPS is faulty, alarm information is displayed on the LCD. Clear critical alarms before 
powering on the UPS again. Otherwise, the fault scope expands or the UPS is damaged. 
Table 8-1 lists the solutions to common faults. 
Table 8-1 Solutions to common faults 
The mains switch is ON. 
The LCD does not display 
anything. The system 
does not perform 
self-tests. 
 
The input 
power supply 
is not 
connected. 
 
The input 
voltage 
exceeds the 
limit. 
 
Check the input power cable 
connection. 
 
Use a multimeter to check that 
the UPS input voltage meets 
specifications. 
The mains is normal, but 
the bypass indicator is off. 
The UPS runs in battery 
mode. 
 
The mains 
switch is 
OFF. 
 
The input 
power cable 
is not 
securely 
connected. 
 
Turn on the mains switch. 
 
Check the input power cable 
connection. 
The UPS does not report 
faults, but has no output 
voltage. 
The output 
power cable is 
not securely 
connected. 
Check the output power cable 
connection. 
The UPS does not start 
after you press   
 
  is not 
pressed long 
enough.   
 
Press    for more than 5 
seconds until you hear a beep 
sound.