Table 9-9 Backup time parameters for the ESS-240V12-7AhBPVBA01 battery pack
(6 kVA, battery eciency assumed as 94%)
Load (%) Load (W) One
Battery
pack
(min)
Two
Battery
packs
(min)
Three
Battery
packs
(min)
Four
Battery
packs
(min)
100% 5400 6 19 29 46
80% 4320 9 25 43 57
50% 2700 19 46 68 92
30% 1620 36 77 120 174
Figure 9-1 Backup time parameters for the ESS-240V12-7AhBPVBA01 battery pack
(6 kVA, battery eciency assumed as 94%)
UPS2000-G- (6 kVA-20 kVA)
User Manual 9 Technical Specications
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 120