Table 9-10 Backup time parameters for the ESS-240V12-9AhBPVBA01 battery
pack (10 kVA, battery eciency assumed as 94%)
Load (%) Load (W) One
Battery
Pack
(min)
Two
Battery
Packs
(min)
Three
Battery
Packs
(min)
Four
Battery
Packs
(min)
100% 9000 4 12 23 32
80% 7200 7 17 29 44
50% 4500 12 32 53 70
30% 2700 26 57 88 125
Figure 9-2 Backup time parameters for the ESS-240V12-9AhBPVBA01 battery pack
(10 kVA, battery eciency assumed as 94%)