Table 9-11 Backup time parameters for the ESS-240V12-9AhBPVBA01 battery
pack (15 kVA, battery eciency assumed as 94%)
Load (%) Load (W) Two
Battery
Packs
(min)
Four
Battery
Packs
(min)
Six Battery
Packs
(min)
Eight
Battery
Packs
(min)
100% 13500 7 19 32 48
80% 10800 9 26 44 57
50% 6750 18 48 70 96
30% 4050 35 79 125 171
Figure 9-3 Backup time parameters for the ESS-240V12-9AhBPVBA01 battery pack
(15 kVA, battery eciency assumed as 94%)
UPS2000-G- (6 kVA-20 kVA)
User Manual 9 Technical Specications
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 122