Table 9-12 Backup time parameters for the ESS-240V12-9AhBPVBA01 battery
pack (20 kVA, battery eciency assumed as 94%)
Load (%) Load (W) Two
Battery
Packs
(min)
Four
Battery
Packs
(min)
Six Battery
Packs
(min)
Eight
Battery
Packs
(min)
100% 18000 4 12 23 32
80% 14400 7 17 29 44
50% 9000 12 32 53 70
30% 5400 26 57 88 125
Figure 9-4 Backup time parameters for the ESS-240V12-9AhBPVBA01 battery pack
(20 kVA, battery eciency assumed as 94%)
UPS2000-G- (6 kVA-20 kVA)
User Manual 9 Technical Specications
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 123