Value Range Preset Value
Time interval 30–180 days 60 days
Voltage 2.33–2.40 V/cell 2.35 V/cell
Max. current
(UPS2000-
G-6KRTS/
UPS2000-
G-10KRTS/
UPS2000-
G-15KRTL/
UPS2000-
G-20KRTL)
1.0–2.0 A (standard
model)
1.0–4.0 A (long
backup time model)
2.0 A
Max. time 600–999 minutes 960 min
Float
Charge
Voltage 2.25–2.30 V/cell 2.25 V/cell
Temp. comp.
coef.
0.0–6.0 mV/(*cell) 3.3 mV/(*cell)
Discharge Max. time
(congurable
in non-
battery
mode)
0–24 hours 16 hours
EOD mode
(congurable
in non-
battery
mode)
Batt. protect rst,
Backup time rst, and
Balanced mode
Backup time rst
EOD auto-
start
(congurable
after the
inverter shuts
down)
Enabled and Disabled Enabled
Bat mode
shut delay
0–600 seconds 0s
Shallow
Discharge
Timed
shallow
discharge test
(UPS2000-
G-15KRTL-01/
UPS2000-
G-20KRTL-01)
Enabled and Disabled Disabled
UPS2000-G- (6 kVA-20 kVA)
User Manual C LCD Menus and Parameters
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 138

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals