Mai
n
Men
u
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range Preset Value
Test
notication
(UPS2000-
G-6KRTS/
UPS2000-
G-10KRTS/
UPS2000-
G-15KRTL/
UPS2000-
G-20KRTL)
Enabled and Disabled Disabled
Time interval 30–90 days 60 days
Discharge
ratio
10%–50% 20%
Settings
wizard
(congur
able
after the
inverter
shuts
down)
Language - English, Chinese,
Spanish, French, and
Russian
English
System
Parameters
Voltage level ● 208 V, 220 V, 230 V,
and 240 V (on the
UPS2000-G-6
kVA/10 kVA)
● 208 V, 220 V, 230 V,
and 240 V, single-
phase (on the
UPS2000-G-15
kVA/20 kVA)
● 380 V, 400 V, and
415 V, three-phase
(on the UPS2000-
G-15 kVA/20 kVA)
● 220 V (on the
UPS2000-G-6
kVA/10 kVA)
● 220 V, single-phase
(on the UPS2000-
G-15 kVA/20 kVA)
● 380 V, three-phase
(on the UPS2000-
G-15 kVA/20 kVA)
Frequency
level
50 Hz, 60 Hz, and
Automatic
50 Hz
Output mode
(congurable
only on the
UPS2000-
G-15 kVA/20
kVA)
Single-phase and
Three-phase
Three-phase (on the
UPS2000-G-15 kVA/20
kVA)
Battery
Parameters
Batteries /
Positive
batteries/
Negative
batteries
16–20 monoblocs 0 monobloc
UPS2000-G- (6 kVA-20 kVA)
User Manual C LCD Menus and Parameters
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 139