Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0029-01 Maintai
n batt.
Minor Automa
tic
The battery backup time is
aected.
Possible causes:
The battery capacity
is incorrectly set.
The battery loop
cannot be
discharged.
The battery capacity
is low.
Measures:
Check whether the
congured battery
capacity matches the
connected battery
capacity.
Check battery
connections and the
status of each
battery.
Contact Huawei
technical support for
repair.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 150