Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0030-01 UPS
inter
overtem
p.
Minor Automa
tic
The power supply from the
UPS and system is not
aected.
Possible causes:
The ambient
temperature exceeds
40°C.
The air channel is
blocked.
The air
lter is
blocked by dust.
The fan is abnormal.
Measures:
Decrease the
ambient
temperature.
Keep the air intake
and exhaust vents of
the UPS
unobstructed.
Clean or replace the
air
lter.
Clean o the foreign
objects around the
fan. If the alarm
persists, contact
Huawei technical
support for repair.