Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0032-01 Batt.
OVP
Critical Automa
tic
An alarm is generated, and
the battery lifespan is
aected.
Possible causes:
The congured
number of batteries
is less than the
actual number.
The actual number
of batteries does not
meet
specications.
The charger is
abnormal.
Measures:
Check that the
congured number
of batteries matches
the actual number.
Check that the actual
number of batteries
meets requirements.
Disconnected the
external battery
charger, check
whether the alarm is
cleared. If not,
contact Huawei
technical support for
repair.
0034-01
Remaini
ng cap.
warning
Minor Automa
tic
If no action is taken,
continued discharge will
result in system shutdown
due to EOD.
Possible cause:
The battery
discharge lasts too
long.
The mains input is
abnormal.
The number of
batteries or battery
capacity is incorrectly
set.
Measure:
Check the mains, and
charge batteries in a
timely manner.
Check the
congured
battery capacity.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 152