Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0131-01 Ambien
t
overtem
peratur
e
Minor Automa
tic
An alarm is generated. Possible causes:
The ambient
temperature in the
UPS equipment room
exceeds the alarm
threshold (default
value: 40°C).
The temperature and
humidity transducer
is faulty.
Measures:
Check the ambient
temperature in the
UPS equipment
room.
Replace the
temperature and
humidity transducer.
0133-01 Ambien
t
underte
mperat
ure
Minor Possible causes:
The ambient
temperature in the
UPS equipment room
is below the alarm
threshold (default
value: 0ºC).
The temperature and
humidity transducer
is faulty.
Measures:
Check the ambient
temperature in the
UPS equipment
room.
Replace the
temperature and
humidity transducer.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 169

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals