Page #178 background image
Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0134-01 Ambien
t
overhu
midity
Minor Possible causes:
The ambient
humidity in the UPS
equipment room
exceeds the alarm
threshold (default
value: 90%).
The temperature and
humidity transducer
is faulty.
Measures:
Check the ambient
temperature in the
UPS equipment
room.
Replace the
temperature and
humidity transducer.
0135-01 Ambien
t
underh
umidity
Minor Possible causes:
The ambient
humidity in the UPS
equipment room is
below the alarm
threshold (default
value: 10%).
The temperature and
humidity transducer
is faulty.
Measures:
Check the ambient
temperature in the
UPS equipment
room.
Replace the
temperature and
humidity transducer.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 170

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals