Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0136-01 Faulty
tempera
ture
and
humidit
y
module
Minor Possible causes: The
temperature and
humidity module is
faulty.
Measures:
Check parameter
settings of the
temperature and
humidity transducer.
Replace the
temperature and
humidity transducer.
0158-01 On
bypass
Minor Automa
tic
If the bypass is abnormal,
the UPS may power o.
Possible causes:
The inverter is not
started.
The load exceeds the
rated inverter
loading capacity.
The inverter is faulty.
Measures:
Check whether other
alarms are
generated. If yes, see
the other handling
methods.
If no, start the UPS
manually.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 171