Alarm
ID-
Cause
ID
Alarm
Name
Alarm
Severit
y
Alarm
Clearan
ce
Mode
Impact on the System Handling Suggestion
0159-01 On
battery
Minor Automa
tic
The UPS may power o if
batteries are abnormal.
Possible causes:
The mains input is
abnormal.
The UPS is in battery
self-check state.
The mains loading
capability is
insucient.
Measures:
Check the mains
input. If the mains
input is abnormal,
wait until the mains
input recovers.
Check whether the
UPS is in battery
self-check state.
Reduce the load or
replace the UPS with
a larger-capacity
UPS.
0340-01
Maint.
breaker
ON
Minor Automa
tic
The UPS transfers to bypass
mode.
Possible cause: The
maintenance circuit
breaker is ON during
UPS maintenance.
Measure: Switch o the
maintenance circuit
breaker after
maintenance.
61440-0
1
Flash
fault
Critical Automa
tic
Files may be damaged. Possible cause: The
ash memory cannot be
properly read or written.
Measure: Contact
Huawei technical
support for repair.
UPS2000-G- (6 kVA-20 kVA)
User Manual D Alarm Handling
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 172

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals