Item Description Defa
ult
Valu
e
Value Range
Temp.
comp.
coef.
Set a oat voltage correction
coecient based on the battery
temperature when a battery
temperature sensor is connected.
The parameter is congurable in any
mode.
3.3
mV/
(*c
ell)
0.0–6.0 mV/
(*cell)
Discharge screen
Figure 4-40 Discharge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 4-30 Discharge screen (UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01)
Item
Description Defa
ult
Valu
e
Value Range
Max.
time
Set the maximum discharge
time. When the discharge time
reaches the value, the UPS
powers o. If you set the value
to 0Hour, the discharge time is
not limited. The parameter is
congurable in non-battery
mode or non-battery ECO
mode.
NOTE
If you expect the battery
discharge time to be greater
than 24 hours, set Max. time
to 0 hour. Otherwise, the
system may power
o.
If you set Max. time to 0 hour,
the battery string may remain
in the small-current discharge
state according to the
proportion of the battery
capacity to the load power,
which
aects the battery
lifecycle.
16
hour
s
0–24 hours
UPS2000-G- (6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 75

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals