Table 4-28 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-G-10KRTS/
UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item Description Default
Value
Value Range
Equalized
charging
Determine whether to enable
equalized charging. The
parameter is congurable in
any mode.
Enabled Disabled,
Enabled
Time
interval
Set the time interval for
equalized charging. The
parameter is congurable in
any mode.
60 days 30–180 days
Voltage Set the battery equalized
voltage. The parameter is
congurable in any mode.
2.35 V/cell 2.33–2.40 V/cell
Max.
current
Set the maximum equalized
current. The parameter is
congurable in any mode.
2.0 A Standard model:
1.0–2.0 A
Long backup
time model:
1.0–4.0 A
Max. time Set the maximum equalized
charge time. The parameter
is congurable in any mode.
960 min 600–999 min
● Float Charge screen
Figure 4-39 Float Charge screen
Table 4-29 Float Charge screen
Item
Description Defa
ult
Valu
e
Value Range
Voltage Set the battery oat voltage. The
parameter is congurable in any
mode.
2.25
V/cell
2.25–2.30 V/cell
UPS2000-G- (6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 74