Item Description Defa
ult
Valu
e
Value Range
Bat
mod
e
shut
delay
When the delay time reaches
the value after UPS transfers to
battery mode, the UPS powers
o. If this parameter is set to
0S, the shutdown delay
function is disabled. If the delay
time is set to other values,
ensure that backup time is
greater than shutdown delay
time of battery mode.
Otherwise, the power supply to
loads may be disconnected. The
parameter is
congurable in
non-battery mode or non-
battery ECO mode.
NOTE
If the mains input and bypass
input use the same power
source, the system powers
o
when the shutdown delay in
battery mode reaches the
preset value. If the mains input
and bypass input use
dierent
power sources, the system
transfers to bypass mode when
the shutdown delay in battery
mode reaches the preset value.
The Bat mode shut delay
parameter is not synchronized
in a parallel system. In a
parallel system, set this
parameter to the same value
for
dierent UPSs.
0s
0–600s
The value interval is 30s.
For example, the value
can be 0s, 30s, 60s, and
90s.
Figure 4-41 Discharge Parameters screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
UPS2000-G- (6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 77

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals