Table 4-31 Discharge parameters (UPS2000-G-6KRTS/UPS2000-G-10KRTS/
UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item Description Defa
ult
Valu
e
Value Range
Max.
time
Set the maximum discharge
time. When the discharge time
reaches the value, the UPS
powers o. If you set the value
to 0Hour, the discharge time is
not limited. The parameter is
congurable in non-battery
mode or non-battery ECO
mode.
NOTE
● If you expect the battery
discharge time to be greater
than 24 hours, set Max. time
to 0 hour. Otherwise, the
system may power
o.
● If you set Max. time to 0 hour,
the battery string may remain
in the small-current discharge
state according to the
proportion of the battery
capacity to the load power,
which
aects the battery
lifecycle.
16
hour
s
0–24 hours
EOD
mod
e
Determine the power backup
time. The parameter is
congurable in non-battery
mode or non-battery ECO
mode.
Backup time
rst: Ensures
system running and has a long
backup time.
Batt. protect
rst: Protects
batteries and extends the
battery lifespan.
Back
up
time
rst
Backup time rst, Batt.
protect rst, Balanced
mode
EOD
auto-
start
Determine whether to
automatically start inverter
output after the mains
becomes normal after EOD. The
parameter is congurable after
the inverter shuts down.
Ena
bled
Disabled, Enabled
UPS2000-G- (6 kVA-20 kVA)