6.2.2.2 Starting the Inverters
Prerequisites
1. The UPSs have been powered on.
2. You have installed and logged in to the app.
Procedure
Step 1 If the alarm indicator on the UPS panel is blinking, view the alarm details on the
app and handle the alarm.
Step 2 Choose Cong > Quick Settings.
1. Set the voltage level and frequency level based on site requirements.
2. Set the battery type, single battery voltage, number of batteries in a battery
string, single battery capacity, and number of battery strings based on site
requirements.
Figure 6-16 Quick Settings
Table 6-2 Quick Settings
Item
Description Setting Value Range
Voltage
level(V)
Species the system output
voltage level. This
parameter is congurable
only after the inverter is
shut down.
Set as
required.
220, 230, and
240. The
default value
is 220.
Frequency
level(Hz)
Species the system output
frequency level. This
parameter is congurable
only after the inverter is
shut down.
Set as
required.
50, 60, and
automatic.
The default
value is 50.
UPS2000-H-(6 kVA-10 kVA)
User Manual 6 Power-On Commissioning
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 110