Item Description Setting Value Range
System time Synchronizes the system
time to the UPS.
- -
Battery type Species the type of
batteries connected to the
UPS.
VRLA batt. VRLA batt.,
Lithium batt.
The default
value is VRLA
batt.
Single
battery
voltage (V)
Species the voltage of
each battery in a battery
string connected in series.
Set this parameter based
on the actual conguration.
This parameter is
congurable in non-
battery mode.
Set as
required.
2, 6, and 12.
The default
value is 0.
Batteries in a
battery
string
Species the number of
batteries in a battery string.
Set this parameter based
on the actual conguration.
This parameter is
congurable in non-
battery mode.
Set as
required.
The value
range
depends on
the voltage of
a single
battery. The
default value
is 0.
Single
battery
capacity
(Ah)
Species the capacity of
each battery in a battery
string connected in series.
This parameter is
congurable in non-
battery mode.
Set as
required.
7–1000. The
default value
is 0.
Number of
battery
strings
Species the number of
battery strings connected in
parallel. This parameter is
congurable in non-
battery mode.
Set as
required.
1–4. The
default value
is 0.
Step 3 The parallel conguration parameters are adaptive. Choose Cong > System
Parameters > Parallel system to manually set the parameters as required.
UPS2000-H-(6 kVA-10 kVA)
User Manual 6 Power-On Commissioning
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 111