Figure 6-17 System Parameters
Table 6-3 Parallel system settings
Item Description Setting Value Range
Single/Parallel Species whether the UPS
works in single mode or
parallel mode. This
parameter is
congurable only after
the inverter is shut
down.
Parallel Single, parallel.
The default
value is Single.
Redundant UPSs Set this parameter based
on load capacity and
redundancy requirements.
This parameter is
congurable only after
the inverter is shut
down.
Set as
required.
0–3. The
default value
is 0.
Parallel ID Species the parallel IDs. Set as
required.
1–4. The
default value
is 1.
Step 4 Check that parameters of the current UPS are automatically synchronized to the
other UPSs in the parallel system.
Figure 6-18 Synchronizing parallel parameters
UPS2000-H-(6 kVA-10 kVA)
User Manual 6 Power-On Commissioning
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 112