UPS5000-E-(50 kVA-300 kVA) 
User Manual (50 kVA Power Modules) 
 
Huawei Proprietary and Confidential                                     
Copyright © Huawei Technologies Co., Ltd. 
 
Context 
 
 
 
Route cables for the UPS from inside out and from bottom up. 
 
A cable entry cabinet can be placed only on the right of the UPS cabinet. 
 
In the scenarios where holes are drilled or covers are removed for routing cables, use 
firestop putty to fill in the gap between the cables and the cabinet after routing cables and 
checking cable connections. 
Procedure 
Step 1  (Optional) Determine the installation position for the cable entry cabinet, and draw mounting 
holes in the installation position based on drawings.   
Figure 3-52 Mounting holes for the cable entry cabinet 
 
 
Step 2  Remove the right and rear covers from the UPS cabinet, and remove the front and rear covers 
from the cable entry cabinet. Put away the removed screws and covers. 
Step 3  Adjust the anchor bolts of the cable entry cabinet to make it flush with the UPS cabinet.