1
UPS5000-A-(60 kVA-120 kVA)-H
Quick Guide
Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.
Issue: 05
Part Number: 31508427
Date: 2019-06-28
1
Overview
1. Before installation, read the user manual carefully to get familiar with product information and
safety precautions.
2. Use insulated tools during installation.
3. Only engineers certified by Huawei or its agents are allowed to install, commission, and
maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS
faults caused are beyond the warranty scope of Huawei.
UPS Model Weight Dimensions (H x W x D)
UPS5000-A-60KTTL-H 140 kg
1020 mm x 440 mm x 850 mm
UPS5000-A-120KTTL-H 170 kg
UPS5000-A-60KTTL-H
UPS5000-A-120KTTL-H
(1) Bypass unit
(2) Power unit
(3) Maintenance
bypass switch

Questions and Answers

  • R
    richardedwardsAug 11, 2025
    What to do if the inverter is abnormal in my Huawei UPS?
    • W
      William SavageAug 12, 2025
      If the inverter in your Huawei UPS is abnormal, it could be due to an output overload or a short-circuit. In this case, reduce the load or troubleshoot the short circuit. Alternatively, the power unit may be faulty, requiring you to replace it.
  • E
    Elizabeth GarciaAug 17, 2025
    Why is the rectifier abnormal in my Huawei UPS?
    • A
      Amy SpencerAug 17, 2025
      An abnormal rectifier in your Huawei UPS can be caused by several factors. The mains voltage may be beyond the allowed range (exceeding 280 V or less than 80 V). Check the mains voltage and contact the electric power company if it's out of range. Also, PFC soft-startup may have failed, requiring you to replace the power unit. It is possible that the power unit is faulty.
  • K
    Karen MeltonAug 25, 2025
    How to fix a Huawei UPS that stays in bypass mode and won't transfer to inverter mode?
    • G
      Gloria PrestonAug 25, 2025
      If your Huawei UPS remains in bypass mode and does not switch to inverter mode, it might be set to ECO mode. To resolve this, set the working mode correctly. Also, the number of bypass transfer times may have reached the upper limit; in this case, choose Clear Faults on the LCD.
  • R
    Robert BoltonAug 29, 2025
    What to do if the bypass is abnormal in Huawei UPS?
    • P
      pearsonadamAug 29, 2025
      If the bypass in your Huawei UPS is abnormal, it could be due to a damaged bypass thyristor, requiring you to replace the bypass unit. Alternatively, the bypass unit may be experiencing overtemperature. To resolve this, reduce the load or improve ventilation.
  • B
    bradleygloriaSep 5, 2025
    Why does the charger generate an alarm in my Huawei UPS?
    • R
      rogersseanSep 5, 2025
      The charger in your Huawei UPS may be generating an alarm for a few reasons. The charger itself may have failed, requiring you to replace the power unit. Also, the charger may be experiencing undervoltage. In this case, check whether the configured number of batteries is correct; if the setting is correct but the alarm persists, replace the power unit.