UPS5000-A-(30 kVA-120 kVA)
User Manual
Issue 17
Date 2024-02-21
HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.

Table of Contents

Questions and Answers

  • A
    Alan ThompsonAug 11, 2025
    What to do if the inverter is abnormal in my Huawei UPS?
    • S
      Scott JacksonAug 12, 2025
      If the inverter in your Huawei UPS is abnormal, it could be due to an output overload or a short-circuit. In this case, reduce the load or troubleshoot the short circuit. Alternatively, the power unit may be faulty, requiring you to replace it.
  • F
    fhaleAug 18, 2025
    Why is the rectifier abnormal in my Huawei UPS?
    • K
      karen36Aug 18, 2025
      An abnormal rectifier in your Huawei UPS can be caused by several factors. The mains voltage may be beyond the allowed range (exceeding 280 V or less than 80 V). Check the mains voltage and contact the electric power company if it's out of range. Also, PFC soft-startup may have failed, requiring you to replace the power unit. It is possible that the power unit is faulty.
  • J
    Julie NealAug 23, 2025
    How to fix a Huawei UPS that stays in bypass mode and won't transfer to inverter mode?
    • A
      andrew23Aug 23, 2025
      If your Huawei UPS remains in bypass mode and does not switch to inverter mode, it might be set to ECO mode. To resolve this, set the working mode correctly. Also, the number of bypass transfer times may have reached the upper limit; in this case, choose Clear Faults on the LCD.
  • J
    Jesse WalterAug 30, 2025
    What to do if the bypass is abnormal in Huawei UPS?
    • T
      Timothy CummingsAug 30, 2025
      If the bypass in your Huawei UPS is abnormal, it could be due to a damaged bypass thyristor, requiring you to replace the bypass unit. Alternatively, the bypass unit may be experiencing overtemperature. To resolve this, reduce the load or improve ventilation.
  • M
    Miranda HoganSep 4, 2025
    Why does the charger generate an alarm in my Huawei UPS?
    • J
      Jessica FloresSep 4, 2025
      The charger in your Huawei UPS may be generating an alarm for a few reasons. The charger itself may have failed, requiring you to replace the power unit. Also, the charger may be experiencing undervoltage. In this case, check whether the configured number of batteries is correct; if the setting is correct but the alarm persists, replace the power unit.

Huawei UPS5000-A-30KTTL Specifications

General IconGeneral
ModelUPS5000-A-30KTTL
CategoryUPS
Power Rating30 kVA
Rated Capacity30 kVA / 27 kW
PhaseThree-phase
Operating Temperature0°C to 40°C
Communication InterfaceSNMP, Modbus
Input Voltage380/400/415 V
Output Voltage380/400/415 V
Input Frequency50/60 Hz
Output Frequency50/60 Hz
Output Frequency (Battery Mode)50/60 Hz
Efficiency (AC-AC)Up to 96%
EfficiencyUp to 96%
Battery TypeVRLA
Battery Voltage384 V
Battery CapacityConfigurable
Relative Humidity0–95% (non-condensing)
Communication PortsDry contacts, RS485, USB
Noise Level< 65 dB(A)
Capacity30 kVA
Input Voltage Range305-477 Vac