5.5 Starting the Inverter
UPS System User List
Default User Preset Password
admin (administrator) LCD 000001
WEB Changeme
operator (common user) LCD 000001
WEB Changeme
Change the password after your rst login to prevent unauthorized access. You can choose
System Info > Settings > User Settings and change Password.
Starting the Inverter on the LCD
Step 1 On the main menu screen, tap Control. On the login screen, enter a password.
Step 2 Tap Startup and press to start the inverter.
----End
Starting the Inverter on the WebUI
Step 1 Open a browser (Chrome, Firefox, or Edge are supported). Take Edge as an
example. Choose Settings > Default browser and set Allow sites to be reloaded
in Internet Explorer mode (IE mode) to Allow.
Step 2 Click the Advanced tab, check that Use TLS 1.2 and Use TLS 1.3 are selected, and
click OK.
Step 3 In the address box of the browser, enter https://
UPS IP address
.
Step 4 Enter the correct user name and password and click Login.
Step 5 On the WebUI, choose Monitoring > UPS System > Running Control, and click
Inv. ON, and conrm the operation to start the inverter.
If the power module receives a startup command when it cannot be started, the startup
command will be retained for 1 minute. Within 1 minute, if there is no situation (for
example, the power module encounters other faults, executes a shutdown command, or a
fault is rectied) that requires the startup command to be cleared and the power module
becomes able to start, then the power module responds to the startup command.
----End
UPS5000-A-(30 kVA-120 kVA)
User Manual 5 Single UPS Commissioning
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 128