UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Alarm
ID
(Alarm
ID-Caus
e ID)
UPS is not
normal, and
transfers to
bypass mode.
The
configured
rack address
conflicts with
another one.
Check the rack address setting.
The load
is
excessive.
The rack
capacity
setting is
not
appropriat
e.
Check the load and remove
some loads or expand the UPS
power capacity if the UPS is
overloaded.
Check that the configured rack
capacity meets requirements.
I2C
communicati
on with the
dry contact
board
MUE05A
fails.
Replace the dry contact board
MUE05A.
I2C
communicati
on with the
dry contact
board
MUE06A
fails.
Replace the dry contact board
MUE06A.
The UPS is
working in
battery mode.
The running status is displayed. See
details about how to handle other
alarms.
The running status is displayed. See
details about how to handle other
alarms.
The running status is displayed. See
details about how to handle other
alarms.
The running status is displayed. No
further measures are required.