FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
8
Item
Technical Specifications
Number of IT
cabinets
6 to 48 cabinets (max. 24 cabinets in the N+1 system; max. 48 cabinets
in the 2N system; max. module length: 15 m)
Equipment room
space
In the scenario where the new main way is deployed, the minimum
floor height is 3.0 m when 2.0 m high IT cabinets are deployed and
is 3.2 m high when 2.2 m high IT cabinets are deployed.
In the scenario where the new main way is not deployed, the
minimum floor height is 2.6 m when 2.0 m high IT cabinets are
deployed and is 2.8 m high when 2.2 m high IT cabinets are
deployed.
Cooling
NetCol5000-C 30 kW chilled water in-row precision air conditioner
Power
distribution
Smart module A: integrated UPS cabinet
Smart module B: precision PDC or new main way
Aisle
1200 mm wide dual-row cold or hot aisle containment