EDS 3000 Operating Manual
PN#02080105 • ELC1603-1752 / 09.16
ELECTRONICS
8. Error messages
If an error is detected, then a corresponding error message appears which must be acknowl-
edged by pressing any key. Possible error messages are as follows:
E.01 The switching points and hysteresis have been set in such a way that the resulting
switch-back point is no longer within the permissible setting range.
Example: Switching point is set to 1000 psi, the hysteresis to 1500 psi.
Action: Correct the settings
E.10 A data error has been detected in the saved settings. Possible causes are strong
electromagnetic interference or a component fault.
Action: Check all the settings (programming enable, switching points, switch-back
points and basic settings) and correct these if necessary. If the errors occur
frequently, please contact HYDAC Service.
E.12: An error has been detected in the stored calibration data. Possible causes are
strong electromagnetic interference or a component fault.
Action: Disconnect the unit and re-connect. If the error message is still displayed,
the unit must be returned to the manufacturer for re-calibration or repair.