10
EDS 3000 Operating Manual
PN#02080105 • ELC1603-1752 / 09.16
ELECTRONICS
6.2 Outline of the Adjustment Menu Points
Setting Display Setting Range Pre-Setting
Switch mode for Switch output 1 (Sm1)
SP / Win SP
Switch output 1 operates in
switch point\hysteresis mode
Switch output 1 operates
in window mode.
Switching direction Switching output 1 (S1)
ON / OFF ON
Normally open function
Normally closed function
Switch-on delay switching output 1 (T
on
1)
0.00 to 99.99s 0
Time in seconds which must elapse,
once the particular switching point has
been reached or exceeded, before
switching will occur
Switch-off delay switching output 1 (T
off
1)
0.00 to 99.99s 0
Time in seconds must elapse, once the
pressure has fallen below the particular
switch-back point, before switching will
occur
The adjustment procedure for switch point
2 is the same as described above.
Primary display
ACT /
Top /
S.P.1 /
S.P.2 /
OFF
ACT
Display value which should remain perma-
nently in the display:
Actual pressure
Pressure peak value
Switch point 1
or 2 setting
display o
(for function, see point 4 “digital display”)
Reset time (RTIM)
(only in primary = “top” setting) Indicates
how long the last peak pressure is shown
on the display