4
EDS 3000 Operating Manual
PN#02080105 • ELC1603-1752 / 09.16
ELECTRONICS
1. Functions of the EDS 3000
Depending on the model, the unit offers the following functions:
• Measuring value indication of the actual pressure in PSI, MPa, bar or in a scale
defined by the user.
• Display of the maximum value or of a pre-set switching point.
• Switching of the switching outputs according to the pressure and the pre-set
switching parameters.
• Analog output.
• Menu for basic settings (adapting the EDS 3000 to the particular application)
• Programming enable.
1.1 Exclusion of Liability
This operating manual was made to the best of our knowledge. Nevertheless and
despite the greatest care, it cannot be excluded that mistakes could have crept in.
Therefore please understand that in the absence of any provisions to the contrary
hereinafter our warranty and liability - for any legal reasons whatsoever - are
exclusion in respect of the information in this operating manual. In particular, we
shall not be liable for lost profit or other financial loss. This exclusion of liability does
not apply to defects which have been deceitfully concealed or whose
absence has been guaranteed, nor in cases of culpable harm to life, physical injury
and damage to health. If we negligently breach any material contractual obligation,
our liability shall be limited to foreseeable damage. Claims due to the Product
Liability shall remain unaffected. In the event of translation, only the original version
of the operating manual in German is legally valid.
2. Mounting
The EDS 3000 can be mounted directly onto a hydraulic block via the pressure
connection, or indirectly using a hose or Minimess line (for torque values, see Point
10 – Technical Specifications). By using a ZBM 3000 or ZBM 3100 mounting clamp,
the EDS 3000 can be mounted on a wall while the hydraulic connection is made
indirectly by using a minimess hose. The unit can be turned through 340° around its
longitudinal axis for optimum alignment. The display and key-pad can also be
turned through 270°. The electrical connection must be carried out by a qualified
electrician according to the relevant regulations of the country concerned. (VDE
0100 in Germany). The pressure switch housing must be earthed correctly at the
same time. When fitting the switch into a hydraulic block it is sufficient if the block
is earthed via the hydraulic system. In the case of a Minimess hose-mounting, the
housing must be earthed separately (e.g. screened line).