Hydraulic separator (low-loss header) provides primary/secondary hydraulic separation, a
microbubble air eliminator and a dirt separator. Air eliminator is installed at the most effective
point, where the fluid is at the highest temperature and lowest pressure.
Secondary pumps to multiple loads or zones. All receive identical temperatures. Note integrated
check valves.
Return lines from loads.
Expansion tank connection (point of no pressure change)should be on the suction side of the
circulator.
Primary pump or boiler circulator into connection at rear of boiler.
Fill station with isolation valve closed, or fill tank.
Figure 25 Primary/Secondary piping concept with hydraulic separator
Pressure relief valve (field-supplied): no isolation valve is permitted between the boiler and relief
valve.
Tridicator or external pressure and temperature gauge (field-supplied).
Microbubble air eliminators are best installed where the fluid is at the highest temperature and
lowest pressure.
Expansion tank connection (point of no pressure change) should be on the suction side of the
circulator.
3.8.2 System piping

Table of Contents

Other manuals for IBC EX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC EX Series and is the answer not in the manual?

IBC EX Series Specifications

General IconGeneral
BrandIBC
ModelEX Series
CategoryBoiler
LanguageEnglish

Related product manuals