IBC EX Series - Venting System Maintenance; Condensate Trap Maintenance; Burner Maintenance

IBC EX Series
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.
Clean and flush out the debris in the condensate
trap base.
4.
Fill the condensate trap to the top
with water.
5.
Reinsert the condensate trap through the metal
plate.
6.
Rotate the elbow, and tighten the union
nut, so that elbow and condensate trap
are secured. Ensure the union nut O-ring
is included. Check for leaks.
78
Section: Service and maintenance