1
SL 45-260
PROPANE CONVERSION PARTS KIT# P
-
170B
120-166 R2
DANGER
Check the rating plate of the boiler
to ensure it is congured for the
fuel you are using.
Failure to perform the proper fuel
conversion when required can
result in an immediate hazard.
Operating any IBC boiler using a
fuel other than the fuel listed on
its rating plate is prohibited. If
these instructions are not followed
exactly, a dangerous situation can
result, leading to re, explosion or
production of carbon monoxide,
which may cause property damage,
personal injury, or loss of life.
NOTE
These instructions are to be closely followed, and referenced to the details in
the boiler’s current certied Installation and Operating Instruction Manual.
The above listed modulating boilers are factory re-tested to operate with natural
gas, or propane as ordered. The rating plate will be marked to indicate which fuel
the particular boiler has been set up with. Firing a boiler with a fuel other than what
is listed on the rating plate is prohibited unless the following conversion procedure
is completed by a qualied technician.
The boiler will automatically de-rate the maximum input at a rate of approximately
2% per 1,000’ above 4,500’. The gas valves zero governor will ensure that the
gas:air mixture is not a󰀨ected at altitude.
Important Note: If converting from Propane to Natural Gas - Order Propane
to Natural Gas Conversion Kit, IBC Part# P-223 from your authorized IBC
Distributor.
MODEL NUMBER NATURAL GAS
TO PROPANE
PROPANE TO
NATURAL GAS
SL 35-199 P-224 P-223
SL 45-260 P-170B P-223
Table 1: Fuel Conversion Kits
INCLUDED WITH CONVERSION KIT
(IBC PART# P-170B)
1 x 6.8mm Orice, Marked 6.80 – IBC Part #180-044
1 x Rating Plate Fuel Overlay - IBC Part# 80-108A
1 x Gas Valve Conversion Label - IBC Part# 80-107B
1 x Installer Identier Label - IBC Part# 80-171A
1 x Instruction Sheet - IBC Part# 120-166 R2
WARNING
This conversion kit shall be installed by a qualied service agency in accordance with the manufacturers
instructions and all applicable codes and requirements of the authority having jurisdiction. If the information
in these instructions is not followed exactly, a re, an explosion or production of carbon monoxide may result
causing property damage, personal injury or loss of life. The qualied service agency is responsible for the
proper installation of this kit. The installation is not proper and complete until the operation of the converted
appliance is checked as specied in the manufacturers instructions supplied with the kit.