Do you have a question about the IBO QB-60 and is the answer not in the manual?
Pump type | Centrifugal |
---|---|
Maximum flow | 60 l/min |
Max Flow Rate | 60 l/min |
Power | 370 W |
Voltage | 220-240 V |
Inlet/Outlet | 1 inch |
Inlet/Outlet Size | 1 inch |
Frequency | 50 Hz |
Read manual before use; device operated only by familiarized persons for safety.
Manual is primary part of contract; failure to follow instructions breaches contract.
Ensure well capacity is sufficient for pump; oversized pumps can cause dry operation.
Not for persons with reduced capacities or without experience, unless supervised.
Surface and booster pumps for household water supply; can increase pressure up to 3 bars.
Negative pressure influenced by vertical distance and suction pipe length/diameter.
Using suction pipes with diameter lower than 1” is prohibited and voids warranty.
Device is for pumping clean water; sand causes wear and requires paid repair.
Install in a closed ventilated room on a levelled plane, protected from humidity and frost.
Power supply must be 230V/50Hz with earthing; manufacturer not liable for lack of proper earthing.
Connect suction pipe with flexible non-collapsible hose to avoid stress transfer to the pump.
Do not use anti-vibration hoses with metal plait on suction side to prevent failure.
Suction pipe must be tight; leaks cause air suction and pump failure.
Fill suction pipe and pump with water before starting to prevent seizure and motor damage.
Network requires overcurrent switch (e.g., M611) and residual current device (max 30 mA).
First start with open taps to pump out air; close taps when pressure switch stops motor.
Adjust switch-on/off pressure by means of screws (range 1.5-4 bar, min difference 1.5 bar).
Check tank air pressure quarterly; fill to 0.2 bar below switch-on pressure, max 3 bar.
Improper tank air pressure causes overload, motor failure, or frequent switch-on/off.
Check filter condition periodically; soiled filters dampen flow and can cause failure.
Protect pump/booster set against frost; damage from frost is not subject to warranty repair.
For periods exceeding one day, unplug; prevent flooding from leaks by ensuring submersion.
Certain pump types require unclogging after standstill by moving the shaft or rotor.
Dispose of used product via selective waste collection systems or return to distributor.
Declaration of conformity with European Parliament and Council Directives (MD, EMC, LVD).
List of pump and booster set series covered by the declaration.
Table detailing technical specifications for various pump models.