Specications
2
Parameters
Caution
Input
• Line Voltage: Universal, 190-630 VAC
• Frequency: 50/60 Hz
• Load Side Monitoring: Optional
Output
• Type: Relay, SPDT
• Voltage Range: 240VAC @ 10A maximum
• Frequency: 50/60 Hz
Control Operating Temperature
• Operating Temperature: -40ºC to +75ºC (-40ºF to +167ºF)
• Storage Temperature: -40ºC to +80ºC (-40ºF to +185ºF)
LCD Operating Temperature
• Operating Temperature: -20ºC to +75ºC (-4ºF to +167ºF)
Mechanical
• Mounting: Surface mount using (2) #8 screws
• Terminations: Screw terminals
• Weight: 12 ounces (341 grams)
Dimensions
• 6 1/2” L, 4 1/4” W, 1 3/8” H
• 16.5 L, 10.8 W, 3.5 H (in cm.)
Phase Unbalance Protection
• Voltage Unbalance: 2-20% adjustable
Over/Under Voltage Protection
• Under Voltage: 2-25% adjustable
• Over Voltage: 2-25% adjustable
Phase Loss Protection
• Phase Loss Condition: Equals 25% of nominal for any given phase; system will shut down
and a fault will be recorded should this occur
Delay on Break Timer
• Control Voltage: 18-240 VAC
• Time Delay: 0 to 10 minutes adjustable
Fault Interrogation Delay
• Time Delay: 0-15 seconds adjustable
• Provides a delay between fault detection and system shutdown - helps to eliminate nuisance
trips or unnecessary shutdowns
Installation of the ICM450 shall be performed by trained technicians only. Adhere to all local
and national electric codes.
Disconnect all power to the system before making any connections.
• Control Voltage: 18-240 VAC
• Frequency: 50/60 Hz