25
Table 8 Con’t—Dry Coil Air Delivery* -- Horizontal and Downflow Discharge --
Unit PGN324--060 (Deduct 10% for 208 Volts)
Unit
Heating
Rise
Range
o
F
(_C)
Motor
Speed
External Static Pressure (in. wc)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
PGN360090
25 -- 55
(14 -- 31)
Low
1
Watts 786 769 754 736 722 705 684 658 616
CFM 2027 1960 1901 1821 1759 1693 1616 1513 1354
Heating Rise
o
F
(
_
C)
33
(19)
34
(19)
36
(20)
37
(21)
38
(21)
40
(22)
42
(23)
45
(25)
50
(28)
Medium
Watts 873 849 833 815 798 782 763 748 704
CFM 2095 2026 1962 1887 1817 1748 1679 1583 1439
Heating Rise
o
F
(
_
C)
32
(18)
33
(19)
34
(19)
36
(20)
37
(21)
39
(21)
40
(22)
43
(24)
47
(26)
High
Watts 1012 993 981 963 948 927 904 886 846
CFM 2184 2109 2036 1963 1886 1812 1729 1647 1496
Heating Rise
o
F
(
_
C)
31
(17)
32
(18)
33
(18)
34
(19)
36
(20)
37
(21)
39
(22)
41
(23)
45
(25)
PGN360115
35 -- 65
(19 -- 36)
Low
1
Watts 786 769 754 736 722 705 684 658 616
CFM 2027 1960 1901 1821 1759 1693 1616 1513 1354
Heating Rise
o
F
(
_
C)
43
(24)
44
(24)
45
(25)
47
(26)
49
(27)
51
(28)
53
(30)
57
(32)
64
(35)
Medium
Watts 873 849 833 815 798 782 763 748 704
CFM 2095 2026 1962 1887 1817 1748 1679 1583 1439
Heating Rise
o
F
(
_
C)
41
(23)
43
(24)
44
(24)
46
(25)
47
(26)
49
(27)
51
(29)
54
(30)
60
(33)
High
Watts 1012 993 981 963 948 927 904 886 846
CFM 2184 2109 2036 1963 1886 1812 1729 1647 1496
Heating Rise
o
F
(
_
C)
39
(22)
41
(23)
42
(24)
44
(24)
46
(25)
48
(26)
50
(28)
52
(29)
58
(32)
PGN360130
40 -- 70
(22 -- 39)
Low
1
Watts 786 769 754 736 722 705 684 658 616
CFM 2027 1960 1901 1821 1759 1693 1616 1513 1354
Heating Rise
o
F
(
_
C)
48
(27)
50
(28)
51
(28)
54
(30)
55
(31)
58
(32)
60
(34)
64
(36)
NA
Medium
Watts 873 849 833 815 798 782 763 748 704
CFM 2095 2026 1962 1887 1817 1748 1679 1583 1439
Heating Rise
o
F
(
_
C)
47
(26)
48
(27)
50
(28)
52
(29)
54
(30)
56
(31)
58
(32)
62
(34)
68
(38)
High
Watts 1012 993 981 963 948 927 904 886 846
CFM 2184 2109 2036 1963 1886 1812 1729 1647 1496
Heating Rise
o
F
(
_
C)
45
(25)
46
(26)
48
(27)
50
(28)
52
(29)
54
(30)
56
(31)
59
(33)
65
(36)
*Air delivery values are without air filter and are for dry coil (see Wet Coil Pressure Drop table).
1
Factory--shipped heating/cooling speed
“NA” = Not allowed for heating speed
Note: Deduct field--supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
Table 8— PGN3 Wet Coil Pressure Drop
UNIT SIZE
STANDARD CFM (S.C.F.M.)
600 700 800 900 1000 1 100 1200 1300 1400 1500 1600 1700 1800 1900 2000
024 0.030 0.037 0.044 0.053 0.063 -- -- -- -- -- -- -- -- -- --
030 -- 0.037 0.044 0.053 0.063 0.072 0.081 0.105 -- -- -- -- -- -- --
036 -- -- -- 0.05 0.061 0.072 0.08 0.09 0.11 -- -- -- -- -- --
042 -- -- -- -- 0.044 0.051 0.059 0.065 0.072 0.080 0.088 0.095 0.105 -- --
048 -- -- -- -- -- -- 0.044 0.050 0.053 0.059 0.066 0.072 0.077 0.086 --
060 -- -- -- -- -- -- -- -- -- 0.079 0.087 0.095 0.102 0.113 0.123